BS EN 1996-1-1: design of masonry structures and the UK National Annex
Most of the existing building stock we appraise is masonry, and most of the alterations we design load it. Eurocode 6 replaced BS 5628 in 2010. The UK National Annex mandates the method for masonry strength, sets the material factors, and the standard's rules on slenderness, openings and bearings decide whether a wall works.
What is BS EN 1996-1-1?
BS EN 1996-1-1 is Eurocode 6, the standard for the design of masonry structures, used in the UK with its National Annex. The National Annex mandates Equation 3.1 for masonry strength with its own K factors, sets the material partial factors by unit category and execution class, and prescribes the mortar designations. The standard's rules on effective height, openings and bearings decide whether an altered wall works. It replaced BS 5628, withdrawn in 2010.
- Strength by Equation 3.1, mandated at NA.2.4
- Material factors 2.3 to 3.0 from Table NA.1
- Timber floors give no slenderness relief
- Bearings to clause 6.1.3
Scope and status
BS EN 1996-1-1, Eurocode 6 Part 1-1: Design of masonry structures, General rules for reinforced and unreinforced masonry structures, is used in the UK with its National Annex and replaced BS 5628, withdrawn in 2010. Part 2 covers design considerations, materials and execution, and Part 3 gives simplified methods. For an existing building designed to BS 5628 the old code is read to understand the original design; the assessment is to Eurocode 6.
Masonry is the material where the National Annex changes most. It mandates the method for strength, replaces the strength constants, sets the material factors by execution class and unit category, and prescribes the mortar mixes. A masonry calculation prepared from the Eurocode's recommended values alone is not a UK calculation.
Characteristic compressive strength: the mandated method
Clause NA.2.4 of the UK National Annex mandates option (i) of clause 3.6.1.2(1): the characteristic compressive strength of masonry is found from Equation 3.1, fk equal to K multiplied by the unit strength fb raised to the power alpha and the mortar strength fm raised to the power beta. For general purpose mortar alpha is 0.7 and beta is 0.3. The constant K is read from Table NA.4: 0.50 for Group 1 clay units in general purpose mortar, 0.40 for Group 2 clay units, 0.55 for Group 1 aggregate concrete units and 0.45 for Group 1 dimensioned natural stone.
The equation has limits that are part of the rule: the unit strength fb is not taken above 110 N/mm2 with general purpose mortar, and the mortar strength fm is not taken above twice fb nor above 12 N/mm2. The prescribed mortar mixes M12 to M2, designations (i) to (iv), are in Table NA.2, which is what lets a specification say "designation (iii)" and mean something a checker can test.
Material partial factors
Table NA.1 gives gamma M by the category of the units and the class of execution control. For unreinforced masonry in compression with Category I units it is 2.3 under execution class 1 and 2.7 under class 2; with Category II units 2.6 and 3.0. For unreinforced masonry in shear it is 2.5 under either class. At the serviceability limit state gamma M is 1.0, at NA.2.2.
The execution class is a statement about site control that the designer makes and the specification has to deliver. Designing to class 1 and building to class 2 has removed about 15 per cent of the wall's design strength without anyone noticing, which is why our packages state the class assumed and the specification states what it requires.
Slenderness, effective height and openings
The effective height of a wall is its clear height multiplied by a reduction factor rho that depends on the restraint at its edges, Equation 5.2. The rule most often missed on domestic and tenement work is the one for floors: where a wall is restrained by timber floors or roofs, rho 2 is 1.0 under Equation 5.5. The 0.75 of Equation 5.3 is for reinforced concrete floors only, so a timber-floored house or tenement gets no slenderness relief from its floors. A wall treated as restrained top and bottom only may be taken as such where it is stiffened on two vertical edges at a length of at least 30 times its thickness, or on one edge at 15 times, under 5.5.1.2(7).
Openings change the restraint. Under 5.5.1.2(9) an opening with a clear height greater than a quarter of the wall's clear height, or a clear width greater than a quarter of the wall's length, or an area greater than a tenth of the wall's area, makes the edge of the opening a free edge for effective height. A new opening in a load-bearing wall therefore does more than remove masonry; it can change the slenderness of what remains. Clause 5.5.1.2(11)(iii) gives the relief for a wall stiffened on one vertical edge, Equations 5.6 and 5.7, with an initial eccentricity of the effective height over 450 at 5.5.1.1(4). The vertical resistance of a single-leaf wall is then its capacity reduction factor times its thickness times its design strength, Equation 6.2, with the reduction factor from Annex G.
Concentrated loads at bearings
Where a beam bears on masonry, clause 6.1.3 governs. The resistance is an enhancement factor beta times the bearing area times the design strength, Equation 6.10, with beta from Equation 6.11 and not less than 1.0 nor more than the lesser of 1.5 and 1.25 plus the edge distance term, and the bearing area limited to 0.45 of the effective area. The eccentricity of the load at the bearing is not to exceed a quarter of the wall thickness, at 6.1.3(4); the load must bear on a Group 1 unit or other solid material, spreading at 60 degrees to its base and on one side only at an end bearing, at 6.1.3(6); and with a spreader of the wall's width, at least 200 mm high and three times the bearing length, the stress beneath may reach 1.5 times the design strength, at 6.1.3(7). Clause 6.1.3(5) still requires the wall below to be checked at mid height with its other vertical load.
This is the clause behind every padstone we specify for a load-bearing wall removal or a new opening, and the one most often absent from a package that has sized the beam and stopped. The Eurocodes hub sets out the wider suite, and BS EN 1990 the combinations the wall is checked under.
Documents cited
- BS EN 1996-1-1:2005, Eurocode 6: Design of masonry structures, Part 1-1, clauses 3.6.1.2, 5.5.1.1(4), 5.5.1.2(7), (9) and (11), 5.5.1.3, 6.1.2.1, 6.1.3(4) to (7), Equations 3.1, 5.2 to 5.7, 6.2, 6.10 and 6.11, and Annex G.
- NA to BS EN 1996-1-1:2005, UK National Annex to Eurocode 6, Part 1-1, clauses NA.2.2 and NA.2.4, Tables NA.1, NA.2 and NA.4 and the limits on Equation 3.1.
- BS 5628 (withdrawn 2010), for the record of what it replaced.
Common questions
How is masonry compressive strength determined in the UK?
By Equation 3.1 of BS EN 1996-1-1, fk = K fb^alpha fm^beta, which clause NA.2.4 of the UK National Annex mandates. K comes from Table NA.4, for example 0.50 for Group 1 clay units in general purpose mortar, with alpha 0.7 and beta 0.3.
What partial factor applies to masonry in compression?
From Table NA.1 of the UK National Annex: 2.3 or 2.7 for Category I units under execution class 1 or 2, and 2.6 or 3.0 for Category II units. Shear is 2.5 under either class.
Do timber floors reduce the effective height of a masonry wall?
No. Under Equation 5.5 the reduction factor rho 2 is 1.0 for walls restrained by timber floors or roofs. The 0.75 of Equation 5.3 applies to reinforced concrete floors only.
When does an opening create a free edge?
Under clause 5.5.1.2(9), where the opening's clear height exceeds a quarter of the wall's clear height, or its clear width exceeds a quarter of the wall's length, or its area exceeds a tenth of the wall's area.