BS EN 1991-1-3: snow loads and the UK National Annex

Snow is a UK map, an altitude correction, a shape coefficient and, where a roof meets a taller one or a parapet, a drift. The UK National Annex changes the route at several of those steps, and a snow calculation that follows the Eurocode's own text is wrong in the UK more often than not.

How we work

How are snow loads calculated in the UK?

To BS EN 1991-1-3 with the UK National Annex. The ground snow load is read from the National Annex map, Figure NA.1, and corrected for altitude by Equation NA.1; the exposure and thermal coefficients are both 1.0 in the UK; and drifts against taller buildings, parapets and obstructions are assessed with Annex B of the Eurocode, as accidental actions, in place of the Eurocode's own clauses 5.3.6 and 6.2(2). It replaced BS 6399-3 in 2010.

  • Ground load from Figure NA.1 and Equation NA.1
  • Ce and Ct fixed at 1.0 in the UK
  • Drifts by Annex B, as accidental actions
  • Replaced BS 6399-3, withdrawn 2010

Scope and the UK route

BS EN 1991-1-3, Eurocode 1 Part 1-3: General actions, Snow loads, gives the snow load on a roof from a characteristic ground snow load, a shape coefficient for the roof form, and exposure and thermal coefficients. The UK National Annex supplies the map, fixes the coefficients and, for drifting, substitutes its own route for the Eurocode's. It replaced the snow provisions of BS 6399-3, withdrawn in 2010.

The characteristic ground snow load comes from Figure NA.1, a zoned map of the UK, with the zone value at 100 m above sea level and Equation NA.1 adjusting for the site altitude. The zone values read 0.30 kN/m2 in Zone 1 rising to 0.70 in Zone 5, with a 0.85 contour in the far north. London reads Zone 3; the sparse Zone 1 hatching in England is confined to parts of the south west and Hampshire, and reading London as Zone 1 is an error we have seen in supplied calculations.

Two points about the map are worth stating because they go wrong. The published National Annex carries an amendment note changing the altitude term in Equation NA.1 from A plus 100 to A minus 100, so an uncorrected first printing gives the wrong ground load. And the parent Eurocode's own Annex C, Table C.1, contains a United Kingdom and Republic of Ireland expression that software prints when run on recommended values; it is not the UK route and gives a different number from Equation NA.1 at the same site.

Coefficients the National Annex fixes

In the UK the exposure coefficient Ce and the thermal coefficient Ct are both 1.0 for all topographies and all roofing materials, at clauses NA.2.15 and NA.2.16. The Eurocode offers reductions for windswept sites and increases for sheltered ones, and a thermal reduction for roofs with high heat loss; none applies in the UK, and a calculation that has taken Ce at 0.8 for an exposed site has reduced the load without authority.

For cylindrical and barrel roofs the National Annex replaces the Eurocode's drifted case at clause 5.3.5(3) with its own Figure NA.3 and Table NA.2, at NA.2.20, indexed on an angle alpha measured from the horizontal to the line from crown to eaves, with a separate angle delta to the tangent at the eaves. The drifted arrangement is considered only where alpha exceeds 15 degrees. The two angles are easy to confuse and the shape coefficient depends on which one is used; it is a case where the package has to show the geometry.

Drifting: Annex B, and why drifts are accidental

This is where the UK route departs most from the Eurocode's text. For roofs abutting and close to taller construction, clauses NA.2.21 and NA.2.22 both direct that Annex B of BS EN 1991-1-3 is used to determine the drifted load case, so the Eurocode's own clause 5.3.6 and its shape coefficient are not the UK route and give a different and, in our experience, non-conservative answer. For drifting at parapets and obstructions, Annex B is used in place of clause 6.2(2), at NA.2.7, NA.2.12 and NA.2.23.

Drift loads found from Annex B are treated as accidental actions, at NA.2.5 and NA.2.26. That changes the combination: the drift is checked at a partial factor of 1.0, with no other variable action alongside it, and with no snow elsewhere on the roof. A drift checked as an ordinary variable action at 1.5 is over-designed; a roof where the drift was never checked at all, because the engineer followed the Eurocode's text and not the National Annex, is the more common and more serious finding.

Annex B gives the drift geometry. For a roof abutting a taller structure the shape coefficient is the least of 2h divided by the ground snow load, 2b divided by the drift length and 8, with the drift length the least of 5h, the width of the taller roof and 15 m. For small obstructions, Annex B4 allows the drift to be ignored where the vertical elevation against which it could form is not greater than 1 m2, which settles most chimneys and vent stacks. For parapets the coefficient is capped at 8 and the drift length at 15 m in the same way.

Where it goes wrong

The commonest errors, in the order we find them: using the Eurocode's clause 5.3.6 for a roof against a taller building instead of Annex B; applying Ce below 1.0; reading the ground load from software run on recommended values rather than the National Annex map and equation; omitting the drift case entirely; treating the drift as a variable rather than an accidental action; and, on curved roofs, reading the shape coefficient against the wrong angle. Each one is a statement about which document and which clause was followed, which is why the package names them.

Return period adjustment under Annex D is permitted in the UK only for annual probabilities of exceedance smaller than 0.2, at NA.3.2, so a 30-year return period for a temporary structure is allowed and a 5-year one is not. Snow on a roof that also carries new plant or a maintenance load is combined to BS EN 1990 with the imposed roof load from BS EN 1991-1-1; the two do not act together. Our wind and snow loading assessments and roof loading appraisals are prepared on this route.

Documents cited

  • BS EN 1991-1-3:2003, Eurocode 1: Actions on structures, Part 1-3: General actions, Snow loads, clauses 5.3.5 and 5.3.6, Annex B (B3 and B4), Annex C Table C.1 and Annex D.
  • NA to BS EN 1991-1-3:2003, UK National Annex to Eurocode 1, Part 1-3, Figure NA.1 and Equation NA.1 with its amendment note, clauses NA.2.5, NA.2.7, NA.2.12, NA.2.15, NA.2.16, NA.2.19 to NA.2.23, NA.2.26 and NA.3.2, Figure NA.3 and Table NA.2.

Last reviewed 2026-11-08. Each citation above was checked against the document and edition named. This page describes the standards; it is not a design, and it does not replace a calculation prepared for a specific structure.

Questions

Common questions

Where does the UK ground snow load come from?

Figure NA.1 of the UK National Annex to BS EN 1991-1-3, a zoned map giving the load at 100 m altitude, adjusted for the site altitude by Equation NA.1. Not from the parent Eurocode's Annex C Table C.1, which software prints when run on recommended values.

Does the exposure coefficient reduce snow load on an exposed site in the UK?

No. The UK National Annex fixes Ce and Ct at 1.0 for all topographies and roofing materials, at NA.2.15 and NA.2.16.

How is snow drift against a taller building assessed in the UK?

Using Annex B of BS EN 1991-1-3, as clauses NA.2.21 and NA.2.22 direct, not the Eurocode's clause 5.3.6. The drift is treated as an accidental action under NA.2.5, checked at a partial factor of 1.0 with no snow elsewhere on the roof.

Can a chimney or vent stack be ignored for drifting?

Annex B4 allows drifting to be ignored where the vertical elevation against which a drift could form is not greater than 1 m2. Larger obstructions and parapets are assessed with the Annex B coefficients.