BS EN 1991-1-1: densities, self-weight and imposed loads with the UK National Annex

The first part of Eurocode 1 gives the weights of materials, the self-weight of construction and the imposed loads on floors and roofs. The UK National Annex replaces several of the Eurocode's recommended values, including the roof loads that govern most appraisals of existing roofs.

How we work

What does BS EN 1991-1-1 cover?

BS EN 1991-1-1 gives the densities of materials, the self-weight of construction and the imposed loads on floors and roofs by category of use. In the UK its National Annex sets the values: 1.5 kN/m2 for a domestic floor, and for roofs accessed only for maintenance 0.6 kN/m2 and 0.9 kN from Table NA.7, replacing the Eurocode's own 0.4 kN/m2 and 1.0 kN. It replaced BS 6399-1 in 2010.

  • Densities in Annex A
  • Imposed floor loads by category
  • UK roof loads from Table NA.7
  • Replaced BS 6399-1, withdrawn 2010

Scope

BS EN 1991-1-1, Eurocode 1 Part 1-1: General actions, Densities, self-weight, imposed loads for buildings, supplies three things a calculation needs before anything else: the densities of construction and stored materials in its Annex A, the self-weight of construction works, and the imposed loads on floors, balconies, stairs and roofs by category of use. It replaced BS 6399-1 and, for imposed roof loads, the relevant part of BS 6399-3, both withdrawn in 2010.

The UK National Annex replaces a number of the Eurocode's recommended values, so a load taken from the Eurocode's tables without checking the National Annex is often wrong for the UK. The roof loads are the clearest case and the one that matters most on the existing buildings we assess.

Imposed floor loads

The Eurocode gives ranges and the National Annex fixes the UK values. For Category A1, self-contained dwellings, the UK National Annex gives a uniformly distributed imposed load of 1.5 kN/m2 and a concentrated load of 2.0 kN. The Eurocode's own range for Category A floors is 1.5 to 2.0 kN/m2, so a designer who takes the top of the range has over-designed a house floor by a third relative to the UK value, and one who applies a European value in a UK appraisal has mis-stated the demand.

Movable partitions are treated as an additional imposed load rather than a dead load: for partitions with a self-weight of up to 1.0 kN per metre of wall, clause 6.3.1.2(8) adds 0.5 kN/m2 to the imposed floor load. It is a small number that is routinely forgotten in fit-out appraisals, where a cellular office is being replaced with something else.

Roof loads: Table NA.7, not Table 6.10

For roofs in Category H, roofs not accessible except for normal maintenance and repair, the Eurocode's Table 6.10 recommends 0.4 kN/m2 and 1.0 kN. The UK National Annex replaces both, in Table NA.7, with 0.6 kN/m2 and 0.9 kN for roof slopes below 30 degrees. Between 30 and 60 degrees the distributed load reduces linearly, as 0.6 multiplied by (60 minus the slope) over 30, and at 60 degrees and steeper it is zero. The notes to the table state that the distributed and the concentrated loads are not applied together, and that the distributed load acts on the whole roof area.

This is the load that governs the appraisal of most industrial and commercial roofs when new plant, a walkway or a maintenance regime is proposed, and it is also the load most often taken from the wrong table. A roof appraised to 0.4 kN/m2 has used the European recommended value, not the UK one. Our roof loading appraisals state the table and the row the load came from for that reason.

Densities worth knowing

Annex A gives nominal densities. Normal-weight concrete is 24.0 kN/m3, with a further 1.0 kN/m3 added for normal percentages of reinforcement and prestressing, so reinforced concrete is taken at 25.0 kN/m3. Lime mortar is 12.0 to 18.0 kN/m3 and lime-cement mortar 18.0 to 20.0. Natural sandstone and greywacke are 21.0 to 27.0 kN/m3 and granite 27.0 to 30.0. Oriented strand board, flake board and wafer board are 7.0 kN/m3, chipboard 7.0 to 8.0, softwood plywood 5.0 and birch plywood 7.0.

For masonry units the table refers out to the product standards EN 771-1 and EN 771-2, which is where a unit density has to be read from. On an existing building the self-weight is measured, not assumed: a stone wall whose density is taken at the bottom of the range when it sits at the top is a quarter light before any imposed load has been applied.

How it is applied in an appraisal

An appraisal of an existing floor or roof establishes the self-weight from what is there, applies the imposed load from the UK National Annex for the use proposed, combines them to BS EN 1990, and compares the demand with the capacity of the members as found. Where the use is changing, the change of use appraisal works through the category change explicitly, because moving from Category A to Category B or C is often the whole reason the floor no longer works.

Snow and wind on the same roof come from BS EN 1991-1-3 and BS EN 1991-1-4; the Category H imposed load is not applied at the same time as snow, which is a combination question that BS EN 1990 and the National Annex settle rather than this part.

Documents cited

  • BS EN 1991-1-1:2002, Eurocode 1: Actions on structures, Part 1-1: General actions, Densities, self-weight, imposed loads for buildings, clause 6.3.1.2(8), Table 6.2, Table 6.10 and Annex A Tables A.1 to A.3.
  • NA to BS EN 1991-1-1:2002, UK National Annex to Eurocode 1, Part 1-1, Category A1 values and Table NA.7 with its notes.

Last reviewed 2026-11-08. Each citation above was checked against the document and edition named. This page describes the standards; it is not a design, and it does not replace a calculation prepared for a specific structure.

Questions

Common questions

What is the imposed load on a domestic floor in the UK?

1.5 kN/m2 distributed and 2.0 kN concentrated for Category A1, self-contained dwellings, from the UK National Annex to BS EN 1991-1-1.

What imposed load applies to a roof that is only accessed for maintenance?

Category H in the UK National Annex, Table NA.7: 0.6 kN/m2 and 0.9 kN for slopes under 30 degrees, reducing to zero at 60 degrees. The Eurocode's own 0.4 kN/m2 and 1.0 kN are replaced and should not be used in the UK.

Are the roof loads applied at the same time as snow?

No. The Category H imposed load and the snow load are separate variable actions; which combinations apply is a BS EN 1990 question, and the distributed and concentrated Category H loads are themselves not applied together.

How is the weight of a partition allowed for?

For movable partitions with a self-weight of up to 1.0 kN per metre run, 0.5 kN/m2 is added to the imposed floor load under clause 6.3.1.2(8). Heavier partitions are allowed for as self-weight at their actual positions.